优势SMC风冷式后冷却器AC4010-04 To get correction factor of 1.35 use ambient temperature correction factor at 20°C. To get outlet air temperature divide 38.5°C from (1) by 1.35 from (2). Outlet temperature = 38.5 ÷ 1.35 = 28.5°C from compressors down to 40°C or less and efficiently remove moisture from the air. The air cooled aftercooler does not require cooling equipment and is free from concerns such as water supply cut-off or freezing. Maintenance is easy and the running cost is reasonable. Compact size and lightweight Uses minimal floor space Built-in drain separator Dust-protecting filter optional Series HAA can cool high temperature compressed air Outlet air temperature can be calculated with inlet air temperature, ambient temperature and amount of air in the following procedure. (Example) Inlet air temperature: 100°C, Ambient temperature: 20°C, Amount of air: 2000 l/min (ANR), Air pressure: 0.7 MPa, Model: HAA22-14 Outlet Air Temperature at Above Conditions Use outlet air temperature of 38.5°C from outlet air temperature table. At this time correction factor line becomes . 优势SMC风冷式后冷却器AC4010-04